Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the RealStream be configured so that an alarm triggers a DO to activate a local autodialer?
There is an Auxiliary Alarm Output sensor. If that sensor is enabled and installed on an IO point (DO), the assigned DO will turn on any time there is an active alarm.
It does not turn on for alerts. The system cannot be configured so that a DO will turn ON only if a specific alarm is raised.
For instance you cannot configure it to turn on if the HH alarm is raised, but not turn on if the LL alarm is raised.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings