Is it possible to set up M580 Hot Standby with mismatched PV and RL versions?

Issue
When the M580 CPUs are received, the hardware versions might not match.

Product Line
M580

Resolution
The PV and RL versions do not need to match in order to use the M580s in a Redundant Configuration. It is important that the firmware loaded into the M580s does match.

If it does not match, Unity Loader (for firmware V3.20 and lower only) can be used to load the latest or matching firmware. https://www.se.com/us/en/download/document/Unity_Loader_V140_SP1/

For the newer V4.xx firmware the EADM tool must be used for upgrade/matching (can also be used with older versions). https://www.se.com/us/en/download/document/EADM/

If it becomes necessary to run mismatched firmware the ECPU_HSBY_1.FW_MISMATCH_ALLOWED component can be set to allow this until the firmware can be matched. This component can be found in the ECPU_HSBY_1 Device DDT variable.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings