Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
CANopen telegram. What is the content of CANopen data frame and its length?

CANopen data frame consists of :
SOF = start of frame (1 bit)
Arbitration field = 12 or 32 bits depending on whether 11 or 29 bit identifier is used (feature of the device)
Control field = 6 bits
Data field depends on mapping. Process data object can carry max 8 bytes. If each variable takes 2bytes then max content of 4 variables in data filed is possible.
CRC = control redundancy check (16 bits)
ACK = acknowledge (2 bits)
EOF = end of frame + intermission (7+3 bits)

Total: 47 bits + data filed (derived from number of variables mapped and their length).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings