Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does ‘Supply Monitoring’ affect over current detect?
Question:
As for the X80 DDO module,
does ‘Supply Monitoring’ affect over current detect? i.e. If I uncheck Supply Monitoring can I assume this channel will no longer trip on over current?

Answer:
No, supply monitoring is only used for supervising the threshold voltage of Pre-actuator. In case it does not exceed the threshold voltage, the output will be off.
The channel over current will be always indicated via LED

Schneider Electric USA

Attachment(s)
SupplyMonitoring.png [123.23 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings