Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the ambient temperature and altitude limits for the Masterpact MTZ?
Issue:
Ambient and Altitude considerations for Masterpact MTZ

Product Line:
Air Circuit Breakers

Resolution:
Ambient temperature:
  • Operating ambient temperatures: -25 C to +70 C
  • Shipping and storage temperatures: -40 C to +85 C
  • Damp heat: relative humidity 95%, temperature +55 C
  • Dry cold temperature tests defined by IEC 60068-2-1
  • Dry heat temperature tests defined by IEC 60068-2-2
  • Damp heat tests defined by IEC 60068-2-30
Altitude:  Up to 2000 m with no derating. Up to 5000 m with derating per ANSI C37.20.1 par. 7.1.4.1

See attachments for more details.

Schneider Electric USA

Attachment(s)
0613HO1805 - US - Masterpact MTZ CB Operating Conditions.pdf [708.78 KB]
Ambient and Altitude from 0614CT1701.pdf [521.14 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings