Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why is my M340 only recognizing modules in the local rack and not the extended one?
Issue
The M340 in the main rack is only recognizing the local IO modules, the expanded rack IO modules are not seen.

Product line
Modicon M340

Resolution
If the software and hardware configurations both match, the issue could be that the cable between the BMXXBE1000 modules is reversed. Power down the backplanes, reverse the cable and power up to see if that resolves the issue.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings