How do you properly connect or wire a transformer with the voltage code SV46 & S46 Rated for 120 x 240V to 16/32V 1Ph
Issue:
How do you properly connect or wire a transformer with the voltage code SV46 & S46?

Product Line:
LV Transformer

Environment:
Applies to Single Phase Transformers with SV46 & S46 voltage code

Resolution:
Primary
- For 240V 1Ph 2W Connect H2 & H3 together and apply primary 240V lines to H1 and H4 (Series Connection)
- For 120V 1Ph 2W Connect H1 and H3 together and connect H2 & H4 together then apply 120V lines to H1 and H4 (Parallel Connections)

Secondary
- For 32V Connect X2 and X3 together and bond to equipment ground or building ground per NEC Code, 32V Outputs are X1 and X4. (Series Connection)
- For 16V Connect X1 and X3 and connect X2 and X4, 16V Outputs are X1 and X4, X2 and X4 and bond to equipment ground or building ground per NEC Code (Parallel Connection)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings