Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Which encoder card for Altivar ATV71 Frequency inverter drives are compatible with sincos encoder?
The only encoder card for ATV71 compatible with sincos encoder is VW3A3409.
Nevertheless, this encoder card cannot be placed in standard ATV71 drive. You have to use ATV71...S383 version (version that could control asynchronous or synchronous motors).
ATV71...S383 is not commercialized, unfortunately, therefore it makes sense to upgrade original assembly to ATV930+ analog encoder card.
FYI, attached is the catalog with encoder cards for ATV71.

Schneider Electric USA

Attachment(s)
altivar71optionsencoderinterfacecards_characteristicsreferencespresentation_en4.1_60285.pdf [73.06 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings