Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What causes a CbF [Circuit Breaker Error] fault on an ATV340 series drive and how do I correct it?
Issue:
How can you resolve a CbF [Circuit Breaker Fault]  on an ATV340 series drive?

Product Line:
ATV340

Environment:
Circuit Breaker Logic function is being used.

Cause:
The DC bus voltage level is not correct compared to the circuit breaker logic control (start or stop pulse)
after the configured timeout [Mains V. time out] LCt.

Resolution:
 Verify the circuit breaker logic control (pulse time for start and stop).
 Verify the mechanical state of the circuit breaker.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings