Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What does the VCPO and VSPO stand for in relation to the MTZ Masterpact breakers?

Article available in these languages: Spanish

Issue:
Looking for VCPO and VSPO option for MTZ masterpact breakers.

Product Line:
ACB Molded Case Circuit Breakers

Resolution:
The VSPO is a handle padlock attachment with keylocks for the OFF position. The VCPO is a handle padlock device with padlocks for the OFF position.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings