Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
2-wire control wiring for ATS...S6 Softstart Controller.
Issue:
2 Wire Control on ATS22 S6

Product Line:
ATS22, Altistart 22

Environment:
All

Cause:
NA

Resolution:
The S6 requires constant 230VAC to terminals CL1 (hot) and CL2 (neutral).

Connect a jumper from Terminal LI1 to LI2.
Close a dry contact between Terminals 24V and LI2 for a run Forward.  Open this connection for a freewheel stop.

For a controlled stop, do not jumper LI1 to LI2. Instead, jumper 24V to LI1 and wire dry contact between 24V and LI2. Program SEt - dEC = ramp down time.

Reference the User manual # BBV51330 or the Quick Start Annex # S1A14738 for more information.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings