Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can I use a Vijeo Designer recipe object from the Webgate ?

Issue:
There are certain limitations while using Recipe objects in Web Gate.

Product Line:
XBTGT
HMIGTO
HMIGTU
IPC with VJD Runtime

Environment:
Vijeo Designer V6.2

Resolution:
The Data Sharing for the recipe control variable (_RecipeControlDefault) must be set to None.
Also the Internal Recipe variables associated to the ingredients must be set to none.
The external Recipe variables associated to the ingredients can be set to Read/Write.





Schneider Electric USA

Attachment(s)
RecipeControlDefault.jpg [211.01 KB]
Recipe.jpg [176.28 KB]
RecipeInternalVariables.jpg [91.86 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings