Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you program a relay on the ATV630 to close at speed reached

Article available in these languages: Spanish

Issue:
Customer wants to have R1 close when motor frequency reaches the reference frequency.

Product Line:
Altivar ATV600 and ATV900

Environment:
All serial numbers

Cause:
Customer set up R1 frequency reference attained.

Resolution:
Check R1 assignment under Complete Settings -> Input/output -> Relay -> R1 Configuration -> R1 assignment ->  [Ref Freq Reached] SrA or Frequency reference reached.
R1A and R1C will close at and above Frequency reference.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings