Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How is a speed pot wired to an Altivar Process Drive?
Issue:
How to wire a speed pot on ATV630 and ATV930 VFDs.

Product Line:
Altivar 630, Altivar 930

Environment:
All

Cause:
Installation

Resolution:
A speed pot typically has 3 terminals
The center terminal is the wiper (the analog signal), and it should be wired to the desired analog input on the drive (AI1, AI2, AI3).
1st leg is wired to +10Vdc.
3rd leg is wired to COM.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings