Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why might I get an NST on my ATV320 when I wire a relay to the digital output (DQ)?
Issue:
Getting NST on my ATV320 when wiring a relay to the digital output (DQ).

Product Line:
Altivar 320

Environment:
All

Cause:
NST on the ATV320 with relay connected

Resolution:
1. Check to make sure your relay is wired correctly in series with the digital output:
Jumper +24V to DQ+
Wire your + side of your relay coil to DQ-
Wire the other side of the coil to COM
2. Measure the amperage pull of your relay. The digital output and the drive's +24V supply each have a maximum 100mA capacity.
If your relay is pulling more than 100mA, it's pulling down the +24V in the drive and causing the NST.
See attachment.

Schneider Electric USA

Attachment(s)
FAQ 86814.png [25.69 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings