Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I setup Clock synchronization between the HMISTU and a M221?
In Vijeo Designer select the target properties and under Startup Options enable Time Management and set Type to PLC Dialog Table.

Please see attachment for more information.

Schneider Electric USA

Attachment(s)
The PLC Real Time Clock.docx [474 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings