Why are ComPact NS/ PowerPact P, R breakers not available in the device selection list of Com’X 210/ 510?

Issue

Why are ComPact NS/ PowerPact P, R breakers not available in the device selection list of Com’X 210/ 510?

How to select a device profile for these breakers during commissioning process?
The ComPact NS/PowerPact P, R breakers discover as MasterPact breakers. ComPact NS/PowerPact P, R breakers do not appear in the device selection list of the Com’X 210/ 510, so user is unable to select these devices.


Product Line
Com'X 210: All firmware versions
Com'X 510: All firmware versions

Environment
ComPact NS/PowerPact P, R breakers on Com’X 210/510 network.

Cause of Issue
Com’X includes support for the MicroLogic trip units A, E, P, H which are used by MasterPact, PowerPact P, R/ComPact NS breakers. Com’ X supports the PowerPact/Compact NS breakers as MasterPact breakers. The PowerPact P, R/ComPact NS do not display in the device selection list.


Resolution
To create a PowerPact P, R/ComPact NS breaker within Com’X:
1.Select a MasterPact breaker with corresponding MicroLogic trip unit (A, E, P, H) from the Device Type drop-down list.
2.Rename it as PowerPact P, R/ComPact NS breaker.
Click Create to create the PowerPact/Compact NS device.
Create New Device setup

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings