Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why are the Trigger Alarm and Run Self-Test buttons grayed out for my unit on the SmartConnect web portal?

Issue:
The Trigger Alarm and Run Self-Test buttons are grayed out for my unit on the SmartConnect web portal.

Products:
SmartConnect Smart-UPS models SMT, SMTL, SMX, SRT

Cause:
SmartConnect control has been disabled on the Smart-UPS.

Solution:
If the Trigger Alarm and Run Self-Test buttons are disabled in the web portal, ensure that SmartConnect access is enabled on your Smart-UPS. From the LCD panel, navigate to Configuration > SmartConnect. The possible settings are Disable or Enable with Ctrl. Enable the setting with Ctrl. Once the change has been made, it will take 5 to 10 minutes to take effect. The web browser will need to be refreshed.



SmartConnect status

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings