Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
In IEC 60870-5-101/104 Master/Client Communication for BMXNOR0200 is it possible to send multiple command from client to server?
Issue
Customer send multiple commands from SCADA within short interval of time ( in ms ). What settings shall be configured in NOR module to accept this commands successfully.

Product Line
BMXNOR0200 V1.7 IR19, WinPP104 ( Licensed Version with customer )

Environment
Windows 10  64 Bit Build 10.1703.1, Control Expert V14.0

Resolution
In the webpage of NOR when configured as server, access the parameter "CMD Queue Size"  by Channel > server > session > paramter > Advanced Properties > CMD Queue Size
This CMD Queue size allows us to configure the NOR to accept multiple commands for various datatypes C_SC, C_SO etc in parallel. By default it is zero. User needs to configure
this value to like 10 to perform some test.

Schneider Electric USA

Attachment(s)
CMD Queue Size.jpg [47.77 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings