Is is possible to use electronic thermal overload relay between Altistart ATS22 or ATS480 or ATS490 or ATS430 and the motor if there are 2 motors in parallel connected to one Altistart?

Yes, it is possible to use LR9D or LR9F electronic relays due to fact that the current has line frequency (50 or 60Hz)