Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the ELM earth leakage module be used for ground fault alarm (without tripping)?
Issue:
Ground fault alarm with ELM

Product Line:
Circuit Breakers

Resolution:
No, the ELM cannot be used as an alarm only device.  Doing so will damage the ELM.
If the alarm only function is required, consider the Square D® Vigirex® ground fault relays.

NOTE: The companion circuit breaker must have an S29392 48 Vdc shunt trip accessory installed.
If shunt trip S29392 is not installed in the circuit breaker, it must be installed before placing into service.

Schneider Electric USA

Attachment(s)
ELM Instr 48041-089-01 2010.pdf [6.17 MB]
Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings