Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the pickup voltage for the RSB series relays?
Issue:
Voltage at which the coil will engage

Product line:
Relays and Timers

Environment:
RSB Zelio Plug in Relays

Cause:
Documents show drop out voltage not pick up voltage

Resolution:
The pickup up voltage is within 70% of the rated coil voltage.

So for example on RSB1A120ED with a 48VDC coil, the pick up voltage is 33.6VDC.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings