Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I configure the ATV930 Process Drive for Positioning by Sensor?
Issue:
ATV930 Positioning by Sensor

Product Line:
Altivar Process Drive

Environment:
ALL

Cause:
Wiring and configuration

Resolution:
ATV900 - Positioning by Sensor

Complete Settings > Generic Functions > Positioning By Sensor
DI1 = Fwd
DI2 = Rev
DI3 = SAF (Stop Fwd)
DI4 = SAR (Stop Rev)
DI5 = DAF (Slow Fwd)
DI6 = SAR (Slow Rev)
**MSTP = Memory Stop = NO (this step is Very Important)
Command and Reference
Ref 1 = AI1
LSP = SLOW Fwd/Rev
(LSP has to be lower than Ref 1)

Note:
Does not work with JOG or PSS
Enable DI1, runs at FR1, Enable DAF drops to LSP, Enable DAF Stops/RDY
Enable DI2, runs at FR1, Enable SAR, drops to LSP, Enable SAF Stops/RDY

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings