Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why is the MS flashing red and NS flashing green on my BMECRA31210?

Article available in these languages: Spanish

Issue
The BMECRA31210 module will not communicate to the M580 and with no Ethernet cables attached is still indicates a flashing red MS and flashing green NS.

Product line
Modicon M580, Modicon X80

Resolution
The flashing red MS indicates a minor fault that should be recoverable.  The above condition could  indicate an invalid address set on the switches. Try rotating each switch all the way around and back to 0 for the Tens and 1 (or drop address) for the Ones. If it does not recover, you could remove the Ethernet cable from the CRA for this test because the goal initially is to get rid of the red MS flashing and after that, attempting communication.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings