Will a shunt trip event be recorded in the Micrologic trip history?
IA shunt trip event will not be recorded in the trip history.
For breaker systems with Modbus connections, Register 12001, Bit 1, can be queried.  This does not apply to Masterpact (always 0) or to PowerPacT P and R frame breakers with motor operators.