" not compatible with State RAM mode."? | Schneider Electric USA" />

Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is Unity Pro Error "IODDT<example> not compatible with State RAM mode."?

Issue
When trying to build an M340 project the error "{Device (x.x) BMX AMx 0<example>}: IODDT "<example>" not compatible with State RAM mode." is reported.

Product line
Unity Pro, Control Expert, Modicon M340

Resolution
This error occurs if the IO modules are mapped as State RAM and the project is trying to use the T_ANA_IN_BMX  IODDT.  This is not allowed. There are certain components that can be used, but not the IODDT in it's entirety.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings