Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is it possible to connect to Altivar drive 6 x PTC sensors if the sensors are connected in star? There are 3 branches with 2xPTC in series. 3 branches are connected to star. Outputs are 3 endpoints and star point

Depending on Altivar type, for example ATV6000, ATV630, ATV930 allows connection of min 1 and max 6 PTC sensors connected in series.
In this case with 6 PTCs if they are connected in star like:
EP1-PTC1-PTC2-STAR,
EP2-PTC3-PTC4-STAR,
EP3-PTC5-PTC6-STAR
(EP means endpoint),

then only 4 PTCs can be connected: ATV(AIx)-EP1-PTC1-PTC2-PTC4-PTC3-EP2-ATV(COM). Star point and third rung with EP3 will remain not connected.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings