Are the plug-in mounting bases for the Powerpact L and the Compact NS630 interchangeable?
Issue:
Can the NSX630 breaker use the Powerpact L mounting base?

Product Line:
Circuit Breakers

Resolution:
These plug-in mounting bases are not interchangeable.
NSX and Powerpact use the same plug-in base AAV41536 (0099539001), but kits LV432516 and S32514 assemblies have a different configuration.
Therefore, the NSX and Powerpact mounting bases cannot be used for the other breaker.