Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to perform a firmware upgrade on a M580 HSBY?
Issue
The M580 HSBY DDT structure has changed and customer needs to follow this procedure where are upgrading the firmware.

Product Line
Unity Pro, Control Expert, BMEH582040, BMEH584040, BMEH586040

Environment
Control Expert v14.0, BMEH584040 v2.90

Resolution
As soon as the firmware upgrade is done then:
  1. Connect to the CPU with Unity Pro/Control Expert (CPU must be in STOP or Run wait)
  2. Use the HSBY_BUILD_OFFLINE EF to pass the CPU in Standby with MOL
Image1

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings