What are the differences between the Wye Primary and Wye Secondary Medium voltage transformers and 5 legged Cores on Medium voltage Transformers?

Article available in these languages: Spanish

Issue:
Does a 5 legged Core Medium voltage transformer isolate the Primary and secondary of Powercast Medium voltage transformers as Terciary wound MV transformers?

Product:
MV Powercast Transformer

Environment:
Application

Cause:
Product Features

Resolution:
Normal delta -wye transformers only require a 3-legged core.
For wye-wye transformers:
  • There can be stray flux heating during unbalanced loading which is why we provide a 4-legged or 5-legged core.  The extra core leg provides a return path for the flux.  This is standard on ALL wye-wye transformers we build.
  • Similarly, a buried tertiary winding provides a path for the balancing current to flow when the secondary must supply an unbalanced load.   A buried tertiary winding is usually only used to accommodate unbalanced loads but can be brought out to a set of external bushings to provide external power.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings