Issue
Converting a project from Concept to Control expert and need to understand the pins.

Product line
Unity Pro, Control Expert

Resolution
**Tip, you do not need the Concept help for READ_REG. The READ_REG is supported in Unity Quantum and you can use 'Help on Type' from the block.**

REQ is the trigger for the block. On the READ_VAR, if you enable EN/ENO, this would be the EN pin.
SLAVEREG is the starting register address of the device that you are reading. On the READ_VAR this is the NUM.
NO_REG is the amount or registers. On the READ_VAR this is NB.
ADDRFLD is the port used to send the message and also the slave device IP address. On the READ_VAR it is the ADR pin which gets tied to an ADDM block.

NDR is the success bit. On the READ_VAR it is the least significant bit of the first GEST word. (GEST[0].0)
ERROR is the indication of a bad read. READ_VAR does not have an error bit, you can create one using GEST[1] <> 0. (Second GEST word not equal to 0).
STATUS is the error code. On the READ_VAR it is the second word of the GEST. (GEST[1]).
REG_READ is the data that is returned from the read. In the READ_VAR it is the RECP.

**Define a value other than 0 for the third word of the GEST. This is the timeout field and if the value is left at 0 and the slave device goes down, the block will lock up indefinitely.**

There is a document attached that outlines the GEST management array and includes a breakdown of the error codes.

Here is a link to a video configuring a READ_VAR and M340. https://www.se.com/us/en/faqs/FA213647/



Schneider Electric USA

Attachment(s)
GEST.pdf [30.33 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings