With M580 is there an Analog Module failure bit that does not set for channel errors?
If you look at the module DeviceDDTname.MOD_FLT this is an error BYTE. MOD_FLT.6 is for module missing or failed. It will not trigger for wiring issues. Bit 0 is also for an internal module failure(present but failed).

See attachment for a breakout of the MOD_FLT bits.




Schneider Electric USA

Attachment(s)
MOD_FLT_BYTE.jpg [215.38 KB]