Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Word order for RealFLO Modbus Registers in an x70 Controller

RealFLO Modbus registers require a word order of “High byte/High word first”.  When running a RealFLO flow computer in a SCADAPack x70 controller, the user must ensure that this is set correctly.
The following screen shots (from Remote Connect) show the proper settings for setting the RealFLO Modbus Registers word order.

1. Ensure that the ‘Realflo Flow Computer’ box is checked in the ‘Project Settings’ dialog








2. Ensure that the word order is set properly in the Modbus | Master/Client | FlowComputer dialog.  The correct setting is 'High byte/High word first'.








3. Ensure the word order is set properly in the Modus | SlaveServer dialog.  The correct setting is 'High byte/High word first'.









With the above settings in place, the modbus registers that contain the flow computer data will display the data correctly.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings