Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to select a CANopen file (*.co) in the TSX CPP 110 configuration screen of Premium platform?
1. Issue

In Unity Pro or EcoStruxure Control Expert software, the following popup could be displayed on TSX CPP 110 screen validation after selecting a *.co file of the Sycon tool:
“Cannot load configuration from the database specified!
Error when reading configuration from DBM file. (…)”
2. Product Line

Unity Pro / EcoStruxure Control Expert, Sycon, TSX CPP 110 CANopen PCMCIA card
3. Resolution

The complete name (path + file name) of the *.co file selected in the TSX CPP 110 screen must be less than or equal to 126 characters.
The directory containing the CANopen file must also have read/write access.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings