Can the NSX cord be routed to the secondary disconnects on a Powerpact H J or L plug-in or drawout breaker?
Issue:
How is the NSX cord routed on a plugin or draw-out Powerpact circuit breaker?

Product line:
Circuit Breakers

Environment:
Powerpact H J L plugin and drawout

Resolution:
The NSX cord cannot connect to the secondary disconnect block on a Powerpact H J or L breaker.  It is routed out of the top of the circuit breaker. It is not connected through the plug-on connectors.
See page 5, attached.

Schneider Electric USA

Attachment(s)
9-Wire Moving Auxiliary Connector for H J L 48940-227-01.pdf [2.27 MB]