Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to Convert the a 32 bit Hex register in Modbus Tester to Decimal Value

Issue
Converting IEEE float to decimal

Product Line
Modbus Tester

Environment
Modbus register conversion

Cause
When using Modbus Tester to read a 32 bit register, the two 16 bit registers need to be converted in order to see the actual value.

Below is an example of reading 32 bit Input Registers:
modbus tester

Resolution
A converter such as IEEE-754  CONVERTER can be used.

The two hex values in each of the 16 bit registers are placed together to obtain the decimal value:
using converter

Modscan was used to validate the results:
modscan


Schneider Electric USA

Attachment(s)
Modbus Tester.zip [91.14 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings