Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the difference between the Model 98 temperature controller and the Model 98A ?

Issue:
What wiring differences are there between the 98 Controller and 98A?

Product:
Powercast MV Transformers

Environment:
Installation

Cause:
Product Features

Resolution:
The Model 98 & Model 98A are physically interchangeable. However, the power connections to the monitors are different. The power is connected to the Model 98 at TB3 pins 3 & 4 (see CONNNECTING TO THE POWER SOURCE beginning on page 8 of the attached Model 98 Instruction Bulletin).

The power is connected to the Model 98A at TB1 pins 13 & 14 and to the fan relays at TB2 pins 3 & 4 (see CONNECTING TO THE POWER SOURCE beginning on page 8 of the attached Model 98A Instruction Bulletin).

When replacing a Model 98 with a Model 98A, connect jumpers from TB2 pins 3 & 4 to TB1 pins 13 & 14 to supply power to the Model 98A.

Schneider Electric USA

Attachment(s)
Model 98A Retrofit Instruction Bulletin.pdf [1.29 MB]
Model 98A Retrofit Instruction Bulletin.pdf [1.29 MB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings