Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the correct 3.3V Power Budget for the BMXDRA0815 module?
Issue
The BMXDRA0815 modules 3.3V Power Budget is incorrect in Control Expert 14 and 14.1.


Product Line
M580
BMXDRA0815


Resolution
The correct 3.3V Power Budget for a BMXDRA0815 is 40ma.

It is incorrectly calculated and displayed as 100ma in CE14 and 14.1.

This issue is corrected in Control Expert version 15.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings