Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to convert DINT&DWORD type to Bit type in Unity Pro and ECE?
  1. Issue
Customer wants to convert DINT variable and DWORD variable to Bit, but there is no such EFB in the library, only WORD_TO_BIT and BYTE_TO_BIT found
  1. Product Line
Unity Pro, Control Expert
  1. Environment
Unity Pro, Control Expert
  1. Resolution
Here is one of the example DFB to convert the  “dint_to_bit” and “dword_to_bit” which can be used to convert the variable type.
I can share you the source code for your reference.


Schneider Electric USA

Attachment(s)
dint_dword_to_bit.rar [2.78 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings