Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What purpose does the fuse of BMXDDI3202 and BMXDDI6402 serve or protect?
  1. Issue

What purpose does the fuse of BMXDDI3202 and BMXDDI6402 serve or protect? and is the information in User manual just an illustration or a mandatory requirement?

  1. Product Line
X80 IO module
  1. Environment
BMXDDI3202, BMXDDI6402
  1. Resolution
This fuse protects both the module and customer power supply. It protects the DDI module when there’s over voltage applied to module. And it protects the sensor power supply in case of the happening of short circuit malfunction inside the module. Since that it’s strongly recommended to apply this fuse.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings