Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can a Buck & Boost Transformer be used to change 240V to 277V?

Issue:
277V is sometimes necessary from a 240V source

Product Line:
LV Transformers

Environment:
Applies to Buck and Boost Transformers by SquareD/Schneider Electric

Cause:
277V is a common voltage for Fluorescent Lighting Ballasts

Resolution:

Yes, Buck & Boost Transformers can be wired for 13.3% change to boost 240V to 272V using wiring diagram #4 in the Buck & Boost Transformer literature, or the Online Buck and Boost Calculator.  See link below.
WARNING: This connection will usually result in both lines being `live`. Some 277V Fluorescent Lighting Ballasts and maintenance personnel who work on them expect one of the lines to be a neutral with insignificant voltage to ground. Load equipment damage or personal injury could result in such applications.



Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings