Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Do Multi 9 breakers have a 480 Vac delta rating?
Issue:
Multi-9 (M9) breaker and 480 Vac breakers

Product Line:
Circuit Breakers

Resolution:
No, the Multi 9 breakers are not rated for 480 Vac delta.

The UL 1077 listed M9 is rated for 480Y/277 Vac, not 480 Vac delta.
The IEC version has a 440 Vac rating.
The UL 489 version has a 480Y/277 Vac rating (0.5 - 20 A), 240 Vac (0.5 - 35 A).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings