Can the amperage be changed on a Micrologic LX, LE, MX, ME, NX, NE, PX, or PE circuit breaker?
Issue:
Need to change the amperage or sensor on a legacy Micrologic electronic trip breaker

Product line:
Legacy Micrologic breakers

Resolution:
To change the amperage of a legacy Micrologic trip breaker, there are two options:  1) change out the rating plug or 2) adjust the long time pickup dial. For safety reasons, ONLY perform work and maintenance on de-energized equipment. There is a possibility of tripping the breaker during adjustments.

The rating plugs with their multiplier values are listed below. The multiplier is the factor to be applied to the sensor rating. Note that there is no restriction on interchanging the ARP rating plugs on LX, LE, MX, ME, NX, NE, PX or PE breakers.

PLEASE NOTE THAT THESE PLUGS ARE OBSOLETE WITH NO REPLACEMENT
Catalog #Multiplier
ARP0400.4
ARP0500.5
ARP0560.563
ARP0580.583
ARP0600.6
ARP0630.625
ARP0670.667
ARP0700.7
ARP0750.75
ARP0800.8
ARP0830.833
ARP0880.875
ARP0900.9
ARP1001

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings