What is the part number for the PA, PH, PC, PX, PE frame key interlock adapter plate? Key lock and installation?
Issue:
How to have Kirk Key Interlock on legacy P-frame
Product Line:
PA, PH, PC, PX, PE
Resolution:
The Kirk key interlock accessory for a PA handle is PAKK. The Kirk key lock type is "F" with 1 inch bolt protection. See attachment for key locking and installation instructions.

Schneider Electric USA

Attachment(s)
PAF kirk key installation.pdf [196.36 KB]