What size hex wrench is needed for the wire binding screw of the AL400LA lug for the LA, LH, and Q4 circuit breakers?
Issue:
What size allen wrench do you need for the  wire binding screw for the AL400LA lug?

Product Line:
Molded case circuit breakers

Resolution:
A 3/8" Allen wrench for the wire binding screw and Torx T40 is the tool used to remove or install the mounting screw.