Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the minimum level of current displayed by Micrologic trip units on Powerpact M, P, and R frame and Masterpact breakers
Issue:
Inaccurate reading on the LCD Display of the Ammeter trip unit

Product Line:
Circuit breaker

Resolution:
With current flow between 0 and 20% of sensor value, the ammeter may not be accurate.
Even with external power supplied, current through the circuit breaker must exceed 0.20 x In for the ammeter reading to be accurate to within 1.5%.

> Below 0.1 x In, measurements are not significant
> Between 0.1 x In and 0.2 x In, accuracy changes linearly from 4% to 1.5%
> Between 0.2 x In and 1.2 x In, accuracy = 1.5%

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings