Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the repair parts for a QO3040L200, series G1 load center?
Issue:
Design repair parts

Product Line:
QO load centers

Resolution:
Only the parts listed below are considered field replaceable.
Cover - QOC30UF for flush, QOC30US for surface
Interior Assembly - QON3040L200
Neutral Bonding Screw - 4028340450
Main Lugs - QOL225
Indoor Cover mounting screw - 4020513002K
Indoor Cover door hinge - 4054541401
Door Latch Kit - 4020284450K

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings