Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can 8903L/LX lighting Contactors be ordered with Normally Closed Power Poles?
Issue:
Needs to know how to order an 8903L lighting contactor with factory configured normally closed power poles

Product Line:
8903 Lighting Contactors

Environment:
NEMA Lighting Contactors

Resolution:
The first digit for 8 poles or fewer devices represent the normally open power poles and the second digit represents the normally closed power poles. For example, Class 8903 Type LO60 provides 6 normally open power poles where Type LO06 provides 6 normally closed power poles and Type LO33 provides 3 normally open and 3 normally closed power poles.

On 10 and 12 pole devices normally open is represented by the first two digits and normally closed by the last two digits .For example, Class 8903 Type LO1200 provides 12 normally open power poles where Type LO0012 provides 12 normally closed power poles and Type LO66 provides 6 normally open and 6 normally closed power poles. There is a maximum of 8 normally closed power poles when used in conjunction with normally open poles.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings