Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can primary breakers be exchanged in Mini-Power Zone Transformers for lower amperage ratings?

Issue:
Mini Power Zone (MPZ) primary main breaker sizing

Product Line:
LV Transformers

Environment:
Applies to Mini Power Zone (MPZ) Transformers by SquareD/Schneider Electric

Cause:
Main breakers for Mini Power Zone (MPZ) Transformers are sized per NEC 450-3b

Resolution:

The primary mains supplied with an MPZ can be replaced by a lower ampacity breaker of the same voltage & AIC ratings and style. Care should be taken not to install a new, lower ampacity breaker which will allow nuisance tripping due to Transformer inrush.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings