Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
I am installing a Uninterrupted Power Source (UPS) system. Can I use a Transformer to convert the output of the UPS to a different voltage?
Issue:
Use of Transformers with UPS systems

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Cause:
Output voltages of UPS systems may require changing to a more suitable level

Resolution:

SquareD/Schneider Electric does not recommend that standard Transformers be connected to the output of UPS systems, or at the load side of adjustable frequency motor drives. Standard Transformers are designed for a maximum of 5% total harmonic voltage distortion on the input, and the output voltage of many UPS systems and drives will exceed that maximum. For further information contact your Distributor or local SquareD/Schneider Electric Sales Office.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings